Citizens Bank of Festus v. Missouri Natural Gas Co.

314 S.W.2d 709, 72 A.L.R. 2d 855, 1958 Mo. LEXIS 701
CourtSupreme Court of Missouri
DecidedJune 9, 1958
Docket46153
StatusPublished
Cited by24 cases

This text of 314 S.W.2d 709 (Citizens Bank of Festus v. Missouri Natural Gas Co.) is published on Counsel Stack Legal Research, covering Supreme Court of Missouri primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Citizens Bank of Festus v. Missouri Natural Gas Co., 314 S.W.2d 709, 72 A.L.R. 2d 855, 1958 Mo. LEXIS 701 (Mo. 1958).

Opinions

[710]*710HYDE, Judge.

Action for $150,000 damages to plaintiff’s building by fire claimed to have been caused by negligence of defendant. Verdict and judgment were for defendant and plaintiff has appealed. Plaintiff alleges trial errors and defendant claims that plaintiff failed to make a case for the jury. We will, therefore, state the facts shown by the evidence from the view most favorable to plaintiff.

Plaintiff alleged that a gas heating unit installed and serviced by defendant was defective and produced heat of such temperature as to cause the building to catch fire. Defendant’s theory was that the fire started under the floor of the second story from the electrical wiring to the east of the heating unit and burned under the floor until it reached the room in which the heating unit was located. There was much electrical equipment in the dentists’ offices with wiring for it under the floor.

Plaintiff’s two story brick building was located at the northwest corner of Main and Adams Street in Festus. Two dentists, Dr. Lea and Dr. Reed, had offices on the second floor. Each had a reception room, a business office room, a laboratory room, a darkroom, and two operating rooms. The floors of these rooms were covered with tile on plywood. Dr. Lea’s offices were in the south part of the second floor and Dr. Reed’s in the north part. In 1954, defendant installed for plaintiff a combination gas operated heating and cooling unit for these second floor offices. It was placed in a small room between the offices of the dentists. This room had only tongue and groove wooden flooring without any plywood or tile over it. The unit was mounted on a wooden platform and it was housed in a metal cabinet. An enclosure of plaster board and wooden studding was built around it, having a wooden door with louvers at the bottom for cold air return. The piping, controls, and enclosure was designed and installed by defendant. Metal ducts led from the top of the unit to all rooms of the dentists’ offices. The only thermostat was on the west wall of Dr. Lea’s north operating room. Dr. Reed had access to it through a door between the two offices and he would turn it down to a 65 degree setting when he left in the afternoon. (The thermostat could be set from 65 to 90 degrees.) The furnace did not heat satisfactorily and many complaints were made to defendant; it was either too hot or too cold and 40 reports of service calls by de^ fendant’s employees were in evidence. (Some of the complaints were because of difference of temperature in the various rooms.) The fire occurred on Sunday, January 22, 1956; and during that month the temperature was frequently 10 to 15 degrees above the thermostat setting.

Three weeks before the fire two of defendant’s employees changed some gas valves on the furnace. On the Thursday before the fire (Jan. 19) the heat was excessive and upon complaint being made, an employee of defendant came and worked on the furnace. Nevertheless, it was very warm both on Friday and Saturday with the thermostat set at 65 degrees. Dr. Lea went to his office on Sunday morning, January 22, at 9:00 to 9:15. He and an attorney, Albert Ennis, entered the building together, with Dr. Lea’s patients, Mr. and Mrs. William Hardin. They entered Dr. Lea’s office and Mrs. Hardin complained of the heat. Dr. Lea examined the thermostat and it was set for 65 degrees; but he said the temperature was over 80 degrees and he made no adjustment or change. Another patient came in while Hardin was in Dr. Lea’s chair, and after he treated both patients they all left about 9:30 a.m. Nothing attracted Dr. Lea’s attention at that time except that it was very warm. There was no fire or flame of any kind in his office when he left. He went to his home and heard the fire siren about 10:00 to 10:15 a.m. When he got down to his office it was on fire, but no water had yet been put on it by the fire department. After the fire had been put out, Dr. Lea went to his office and observed the furnace unit and the [711]*711burned condition of the building. There was a hole burned through the roof above the unit which was larger than the unit and there was a hole burned through the floor of the second story, in front of the furnace unit. The wall was burned out on the left side of the small room enclosing the furnace and all the furniture of his reception room (adjoining the furnace room on the west) was completely burned. The metal door on the heating unit was bent out a foot or more at the upper right hand corner with the other three corners of the metal door of the unit still in place. The partition of his darkroom, which also adjoined the furnace room on the south, was burned out.

When the fire alarm sounded about 10:10 a.m. firemen went immediately to the building. Smoke was coming from the second story windows and some of the firemen entered the ground floor main entrance. One of the firemen noticed sparks coming from the ceiling of the first floor. He said he did not know wether these sparks were fire sparks or electric sparks. He poked a hole through the ceiling at that point, and encountered pipes and metal; he put a 1½ inch hose through the hole and poured water on the fire he then saw but this had no effect on it. He then went outside to the rear of the bank building and turned off all of the gas valves supplying the building, and when he returned the fire which he had been unable to extinguish with water had gone out. He said the roof and ceiling over the unit were burned completely through to the outside, the hole being larger than the size of the unit. The portion of the floor immediately surrounding the furnace room was burned out, and he could see through into the bank below. The wall of the little room which contained the furnace was burned out. The controls and valves and front part of the furnace mechanism inside of the outer shell, were melted, charred and black, and the melted parts had run down. The floor joists of the second floor, running east and west, were burned under the furnace and to within two feet of each wall of the building. Other plaintiff’s witnesses (the Donalds) who repaired the building, found the only floor damage to be along these joists, “from the corridor to the east wall.”

Plaintiff had an expert witness (Mr. Murer) who said if the temperature rose 12 to 15 degrees above the thermostat setting, in his opinion there was something wrong with the controls. In addition to the thermostat there was another safety device called the limit switch which would turn off the gas when the temperature in the furnace bonnet (above the combustion chamber) reached 170 degrees. When operating as a furnace the unit and two gas burners and these controls (if working properly) would shut off the gas when it produced the proper amount of heat. There was also a fan with an automatic control in combination with the limit switch, and when operating it would keep the temperature down. Murer said, if the furnace continued to generate heat after the thermostat setting was reached, this would indicate faulty operation of the thermostat, the fan control, and limit switch control. He said there could be faulty wiring or faulty control valving or a valve could be stuck or have something on it. If all these controls failed, the furnace would continue to generate heat and the unit would eventually be destroyed by catching fire and burning up. He said the control wiring would deteriorate most rapidly, not being designed to operate under excess heat, and excess heat would destroy the aluminum tubing, opening the valve and continuing the flow of gas. Aluminum melts at a lower temperature than grass or steel.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Hanes v. Bacon Sales Co.
602 S.W.2d 50 (Missouri Court of Appeals, 1980)
Myers v. Bi-State Development Agency
567 S.W.2d 638 (Supreme Court of Missouri, 1978)
Sydney v. Coca-Cola Co.
569 S.W.2d 11 (Missouri Court of Appeals, 1978)
Henderson v. W. C. Haas Realty Management, Inc.
561 S.W.2d 382 (Missouri Court of Appeals, 1977)
Winters v. Sears, Roebuck and Co.
554 S.W.2d 565 (Missouri Court of Appeals, 1977)
Jones v. Garney Plumbing Co.
409 S.W.2d 637 (Supreme Court of Missouri, 1966)
Listerman v. Day and Night Plumbing & Heating Serv.
384 S.W.2d 111 (Missouri Court of Appeals, 1964)
Smith v. Middlekauff
359 S.W.2d 755 (Supreme Court of Missouri, 1962)
Hanff v. St. Louis Public Service Company
355 S.W.2d 922 (Supreme Court of Missouri, 1962)
Sutton v. Fox Missouri Theatre Company
356 S.W.2d 41 (Supreme Court of Missouri, 1962)
Goldblatt v. St. Louis Public Service Co.
351 S.W.2d 773 (Supreme Court of Missouri, 1961)
Grote v. Reed
345 S.W.2d 96 (Supreme Court of Missouri, 1961)
Superior Ice & Coal Co. v. Belger Cartage Service, Inc.
337 S.W.2d 897 (Supreme Court of Missouri, 1960)
Journagan v. McElroy
336 S.W.2d 692 (Supreme Court of Missouri, 1960)
Myers v. Buchanan
333 S.W.2d 18 (Supreme Court of Missouri, 1960)
Baccalo v. Nicolosi
332 S.W.2d 854 (Supreme Court of Missouri, 1960)
Paige v. Missouri Pacific Railroad Company
323 S.W.2d 753 (Supreme Court of Missouri, 1959)
Rittershouse v. City of Springfield
319 S.W.2d 518 (Supreme Court of Missouri, 1959)
Trump v. Ballinger
317 S.W.2d 355 (Supreme Court of Missouri, 1958)

Cite This Page — Counsel Stack

Bluebook (online)
314 S.W.2d 709, 72 A.L.R. 2d 855, 1958 Mo. LEXIS 701, Counsel Stack Legal Research, https://law.counselstack.com/opinion/citizens-bank-of-festus-v-missouri-natural-gas-co-mo-1958.