U-Fuel, Inc. (NV) v. Highland Tank & Manufacturing Co.

228 F. Supp. 2d 597, 2002 U.S. Dist. LEXIS 21514, 2002 WL 31445214
CourtDistrict Court, E.D. Pennsylvania
DecidedNovember 4, 2002
DocketCivil Action 02-2723
StatusPublished
Cited by1 cases

This text of 228 F. Supp. 2d 597 (U-Fuel, Inc. (NV) v. Highland Tank & Manufacturing Co.) is published on Counsel Stack Legal Research, covering District Court, E.D. Pennsylvania primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
U-Fuel, Inc. (NV) v. Highland Tank & Manufacturing Co., 228 F. Supp. 2d 597, 2002 U.S. Dist. LEXIS 21514, 2002 WL 31445214 (E.D. Pa. 2002).

Opinion

MEMORANDUM

DuBOIS, District Judge.

I. INTRODUCTION

Plaintiff, U-Fuel, Inc. (“U-Fuel” or “plaintiff’) alleges in this patent infringement action that Highland Tank & Manufacturing Company, Inc. (“Highland”), Steel Tank Institute (“STI”), and Modern Welding Company of Ohio, Inc. (“Modern”) (collectively, “defendants”) infringed U-Fuel’s United States Reissued Patent No. 37,144 (the “'144 patent”) by licensing, manufacturing, and selling non-insulated, above-ground storage tanks (“ASTs”) and marketing such tanks as “fire-resistant.” U-Fuel, Highland, and Modern manufacture and sell ASTs. STI is a non-profit trade association whose members include AST manufacturers. STI’s purpose is to promote the use of high-quality steel tanks which are manufactured by its members to meet fire codes and environmental regulations.

Presently before the Court is plaintiffs Motion for a Preliminary Injunction (Document No. 3, filed May 9, 2002), in which plaintiff seeks an order barring defendants from marketing, selling, offering for sale, distributing, licensing, manufacturing, or using any non-insulated, “fire-resistant” ASTs which infringe the '144 patent. Defendants respond by asserting a number of defenses' — prior art inherently anticipates the '144 patent; plaintiffs claim construction violates the written description requirement of 35 U.S.C. § 112; the allegedly infringing activities of defendants are protected under the intervening rights provision of 35 U.S.C. § 252; plaintiff failed to disclose the best mode in making “fire-resistant” ASTs; inconsistent testimony by plaintiff evidences unclean hands; and plaintiff procured the '144 patent through inequitable conduct — warranting the denial of plaintiffs motion.

For the reasons set forth in this Memorandum, plaintiffs Motion for a Preliminary Injunction is denied.

II. PROCEDURAL HISTORY

U-Fuel filed a Complaint against defendants on May 7, 2002. The Motion for a Preliminary Injunction was filed on May 9, 2002. Defendants responded on June 13, 2002; plaintiff filed a reply on July 17, 2002.

The Court held a hearing on the Motion for a Preliminary Injunction on July 22 through 25, 2002, and granted the parties leave to file supplemental memoranda on the issue of the validity of the reissued '144 patent. Both parties thereafter filed supplemental memoranda. The motion was fully briefed on September 9, 2002.

*599 The Court will now set forth findings of fact and conclusions of law in ruling on plaintiffs Motion for a Preliminary Injunction based on evidence presented at the hearing and the written submissions of the parties.

III. FINDINGS OF FACT

ASTs are used for industrial and commercial purposes to store combustible and flammable liquids such as gasoline. Because of the inherent safety risks that ASTs pose, private and public entities have promulgated standards for the testing and rating of ASTs. Such private entities include Underwriter’s Laboratories, Inc. (“UL”), the National Fire Protection Association (“NFPA”), and Southwest Research Institute (“SwRI”).

The “Standard for Steel Aboveground Tanks for Flammable And Combustible Liquids” (“UL 142”) was created in 1922 by UL and prescribes the' minimum construction standard for single and double wall ASTs. 1 Due to increased demand for ASTs for storing commercial fuel, 2 UL developed an additional performance-based listing, known as the “Standard for Insulated Aboveground Tanks for Flammable and Combustible Liquids” (“UL 2085”), 3 which tested the internal temperature rise of insulated ASTs when subject to an external temperature of 2000 degrees Fahrenheit for not less than two (2) hours. Insulated ASTs are listed as “protected” under UL 2085 if the increase in internal temperature does not exceed 400 degrees Fahrenheit. Non-insulated ASTs are not tested under the UL 2085 standard.

The NFPA is an organization which periodically publishes fire codes and safety use requirements, such as separation distances between an AST and a building, an AST and a public roadway or other property line, and an AST and a fuel dispenser. Defs.’ Ex. 8. Section 2-4.5 of the NFPA 30A, Automotive and Marine Service Station Code (“NFPA 30A”), created the standard for “fire-resistant tanks.” 4 Under Section 2-4.5(a), an AST is listed -as “fire-resistant” if it prevents: (a) the release of liquid; (b) failure of the supports for the tank; and (c) impairment of venting for two (2) hours when tested using “a fire exposure that simulates a high-intensity pool fire, such as that described in UL 2085 ... or equivalent test procedure.” Section 2-4.5(a), NFPA 30A (1996).

In' the late 1980’s and early 1990’s, double wall, non-insulated tanks, constructed in accordance with UL 142, were manufactured and sold as ASTs. 5 These ASTs were non-insulated in that the space between the primary and secondary tank was not filled with insulation (usually a concrete mixture) and they were capable of being monitored for any leakage into this space. Non-insulated ASTs are lighter than insulated tanks and thus more mobile and easier to transport. Testimony of R. Michael Webb, July 23, 2002, at 92. In addition, *600 non-insulated tanks cost approximately fifty percent less than insulated tanks. Testimony of Charles A. Frey, July 24, 2002, at 41-42, 45.

In 1993, STI published the “Standard for Aboveground Tanks With Integral Secondary Containment” (“F921”), a specification standard for double wall, non-insulated tanks made in accordance with UL 142. PL’s Ex. 35. Thousands of ASTs manufactured to this standard were sold by STI members during the 1993-1995 period. Defs.’ Ex. 8. Highland and Modern each sold their own versions of double-wall, non-insulated tanks that conformed to UL 142 during this time period as well. Defs.’ Ex. 9; Defs.’ Ex. 10.

U-Fuel filed a patent application on January 17, 1996 covering the construction of an “improved” AST “fabricated from steel plates of minimum thickness, the sheets being made from a special metal alloy, and the plates welded in a specific way, in order to withstand a 2000"F. environment for a minimum of two hours.” (U.S. Patent No. 5,723,842 (the “'842 patent”), column 2, lines 41-44). The '842 patent was issued by the Patent Office on March 3,1998.

SwRI is an applied research and development non-profit organization which provides standards and protocols for the testing, listing, and labeling of tanks, including ASTs. In 1995, U-Fuel contracted with SwRI to create a testing protocol for its non-insulated ASTs. In the context of the contractual arrangement between U-Fuel and SwRI, U-Fuel’s President R.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Perricone v. Medicis Pharmaceutical Corp.
267 F. Supp. 2d 229 (D. Connecticut, 2003)

Cite This Page — Counsel Stack

Bluebook (online)
228 F. Supp. 2d 597, 2002 U.S. Dist. LEXIS 21514, 2002 WL 31445214, Counsel Stack Legal Research, https://law.counselstack.com/opinion/u-fuel-inc-nv-v-highland-tank-manufacturing-co-paed-2002.