Cartel Capital Corp. v. Fireco of New Jersey

410 A.2d 674, 81 N.J. 548, 19 A.L.R. 4th 310, 1980 N.J. LEXIS 1312
CourtSupreme Court of New Jersey
DecidedJanuary 23, 1980
StatusPublished
Cited by181 cases

This text of 410 A.2d 674 (Cartel Capital Corp. v. Fireco of New Jersey) is published on Counsel Stack Legal Research, covering Supreme Court of New Jersey primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Cartel Capital Corp. v. Fireco of New Jersey, 410 A.2d 674, 81 N.J. 548, 19 A.L.R. 4th 310, 1980 N.J. LEXIS 1312 (N.J. 1980).

Opinion

The opinion of the court was delivered by

SCHREIBER, J.

Plaintiff, Country Burger of Ramsey, Inc. (Country Burger), sued Fireco of New Jersey (Fireco), the retailer, installer and servicer of plaintiff’s fire extinguishing equipment, and Ansul, Inc. (Ansul), manufacturer of that equipment, for property damage caused by a fire during which the equipment allegedly failed to operate. 1 Plaintiff’s cause of action against Ansul was based upon negligence and strict liability arising out of a design defect. The action against Fireco involved strict liability because of the same design defect and negligence in improperly servicing the system. The codefendants asserted cross-claims *554 against each other under the Joint Tortfeasors Contribution Act, N.J.S.A. 2A:53A-1 et seq., and for indemnification.

At the outset of the trial Ansul settled with plaintiff for $50,000, voluntarily dismissed its cross-claims and successfully moved for dismissal of Fireco’s cross-claims. Plaintiff then proceeded against Fireco alone. In response to a set of special interrogatories, the jury found that Fireco was negligent, that Ansul had defectively designed the equipment, and that both the negligence and defect were proximate causes of plaintiff’s damages. The jury determined that plaintiff had also been guilty of negligence. It fixed damages due to the malfunctioning of the fire extinguishing equipment to operate at $113,400 and the percentages of fault as follows: Plaintiff—41%, Fireco—30%, and Ansul—29%. The trial court then entered a judgment in favor of plaintiff for $34,020, plus interest and costs.

Fireco appealed, asserting that the trial court had incorrectly calculated the percentage of fault, and plaintiff cross-appealed, contending that the trial judge erred in reducing the judgment. The Appellate Division, relying upon Cepeda v. Cumberland Engineering Co., 76 N.J. 152 (1978), held that the Comparative Negligence Act was not applicable to strict liability suits and reversed. 161 N.J.Super. 301 (1978). We granted Fireco’s petition and plaintiff’s cross-petition for certification. 78 N.J. 407 (1978).

The facts may be summarized as follows. Country Burger operated a fast food restaurant on Route 17 in Ramsey, New Jersey. At the time of the fire it was housed in a one-story brick structure of approximately 3,900 square feet consisting primarily of a dining area and a kitchen. A counter island in the kitchen contained two grills and four deep-fat fryers. Above the grill was an updraft hood through which an exhaust fan vented air to the outside.

Fireco was a recognized distributor of Ansul equipment. In 1967 Fireco sold and installed an Ansul fire extinguishing system in the restaurant. The system consisted of a tank, piping *555 and ejection nozzles located above and directed toward the grills and fryers. The tank, which was affixed to one side of the counter island, contained a chemical in powder form. A cannister, filled with pressurized liquid carbon dioxide was attached to the tank. When released the carbon dioxide acted as a propellant and forced the chemical through the piping and out the nozzles. The chemical mist would then settle on the area at which the nozzle was directed and suffocate any fire at that location. The heat of a fire would automatically activate the system by melting a link which would release a spring and in turn cause a hammer to break open a seal on the cannister. The equipment could also be activated manually by pulling down on a lever connected to the same hammer which would fracture the cannister seal.

Fireco twice extended the system when additional equipment was added in the restaurant. Following a fire in 1969, it had reset and recharged the Ansul mechanism. In August 1972, Kenneth Hakes, a Fireco serviceman, replaced a broken handle manually used to trigger the activation device. Fireco checked the system about once every six months. Its last inspection prior to the fire was around August 1973.

On November 30, 1973, at about 9:30 p. m. some paper plates which had been stacked on a shelf above the grill fell onto the grill and were ignited. No one was in the kitchen at the time. Two customers seated at the counter alerted the employees. John Foti, Jr., the cook, and David Mandara, the night manager, rushed in and Foti pushed the paper plates to the floor and stomped out the fire. However, grease on the grill and the wall behind the grill were aflame. Mandara used a steel brush to control the fire on the grill. Meanwhile the fire on the wall continued to spread. The air passage through the hood over the grill served as a draft and sucked the flames upward. The Ansul system was not operating and Michael Garamone, another employee, attempted without success to activate it manually by pushing the lever. Mandara and Foti then threw flour on the *556 spreading fire. This was ineffectual. The walls and roof were soon aflame and the building was abandoned when the fire department arrived. By the time the fire was brought under control, the building and its contents were substantially destroyed or damaged.

About a week after the fire, Edward Jacobs, an assistant manager at the restaurant, removed the Ansul tank and cannister from the wall. He noticed the tank was extremely heavy, removed the cap and saw that it was still filled with the chemical powder. On December 21, 1973, David C. Pool, a mechanical engineer, examined the tank, the bottle of carbon dioxide and the activating mechanism. He found that it was inoperable because a screw had been inserted into the handle of the lever from the wrong direction. This prevented the handle from rotating and releasing a coil spring which would have caused the release of the carbon dioxide. If the screw had been placed in the opposite side of the shaft, from right to left, the mechanism would have operated. Pool concluded that there was a design defect because the problem, the possibility of inserting the screw improperly, would have been eliminated if there had been an opening on only one side.

Fireco countered with the testimony of its president George Weise. He had been working with Ansul systems for ten years, and had attended Ansul’s training school where he had been instructed in the use and operation of this particular Ansul unit. He said that the design was proper because a recess around the opening on one side of the shaft accommodated the head of the screw preventing it from protruding. He also testified that it was very difficult to insert the screw incorrectly, that is from left to right. Fireco also attempted to show that its serviceman Hakes, who had begun working for Fireco in July 1972, had attached the new handle properly. However, this was apparently the first occasion on which Hakes performed that assignment. He did not remember if the Ansul manual had instructions concerning a handle change and in any event he had not read any before his visit to Country Burger.

*557 The major thrust of the defense was directed toward plaintiff’s conduct. It attempted to show that plaintiff permitted grease to accumulate on the walls.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Krzykalski v. Tindall
181 A.3d 981 (Supreme Court of New Jersey, 2018)
Mark R. Krzykalski v. David T. Tindall
150 A.3d 1 (New Jersey Superior Court App Division, 2016)
Nye v. Ingersoll-Rand Co.
783 F. Supp. 2d 751 (D. New Jersey, 2011)
R & R Insulation Services, Inc. v. Royal Indemnity Co.
705 S.E.2d 223 (Court of Appeals of Georgia, 2010)
Cockerline v. Menendez
988 A.2d 575 (New Jersey Superior Court App Division, 2010)
Vernet v. Serrano-Torres
566 F.3d 254 (First Circuit, 2009)
Kas Oriental Rugs, Inc. v. Ellman
926 A.2d 387 (New Jersey Superior Court App Division, 2007)
Newman v. Isuzu Motors America
842 A.2d 255 (New Jersey Superior Court App Division, 2004)
Burt v. W. Jersey Health Systems
771 A.2d 683 (New Jersey Superior Court App Division, 2001)
Naporano Iron & Metal Co. v. American Crane Corp.
79 F. Supp. 2d 494 (D. New Jersey, 2000)
Ronson v. Talesnick
33 F. Supp. 2d 347 (D. New Jersey, 1999)
Cruz-Mendez v. ISU/Insurance Services
722 A.2d 515 (Supreme Court of New Jersey, 1999)

Cite This Page — Counsel Stack

Bluebook (online)
410 A.2d 674, 81 N.J. 548, 19 A.L.R. 4th 310, 1980 N.J. LEXIS 1312, Counsel Stack Legal Research, https://law.counselstack.com/opinion/cartel-capital-corp-v-fireco-of-new-jersey-nj-1980.