§ 15A-5-304 — Amendments and additions to NFPA related to Automatic Fire Sprinklers Systems.

Utah § 15A-5-304
JurisdictionUtah
Title 15AState Construction and Fire Codes Act
Ch. 15A-5State Fire Code Act
Part 15A-5-3Amendments and Additions to National Fire Protection Association Incorporated as Part of State Fire Code

This text of Utah § 15A-5-304 (Amendments and additions to NFPA related to Automatic Fire Sprinklers Systems.) is published on Counsel Stack Legal Research, covering Utah primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Utah Code Ann. § 15A-5-304 (2026).

Text

(1)NFPA 13, Installation of Sprinkler Systems, 2019 edition.
(1)(a) NFPA 13, Chapter 16, Section 16.9.11, Floor Control Valve Assemblies, Subsection 16.9.11.5, is deleted and rewritten as follows: "16.9.11.5, System Subdivision - Floor/Zone Control Valves. Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet."
(1)(b) NFPA 13, Chapter 8, Section 16.11.2.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "16.11.2.1.1 Single Tenant Occupancies. When a fire alarm system is not required by IFC, Section 907.2, an approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, in a normally occupied location, to aler

Free access — add to your briefcase to read the full text and ask questions with AI

Legislative History

Amended by Chapter 95, 2023 General Session