§ 15A-5-204 — Amendments and additions to IFC related to fire protection and life safety systems.

Utah § 15A-5-204
JurisdictionUtah
Title 15AState Construction and Fire Codes Act
Ch. 15A-5State Fire Code Act
Part 15A-5-2Statewide Amendments and Additions to International Fire Code Incorporated as Part of State Fire Code

This text of Utah § 15A-5-204 (Amendments and additions to IFC related to fire protection and life safety systems.) is published on Counsel Stack Legal Research, covering Utah primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Utah Code Ann. § 15A-5-204 (2026).

Text

For IFC, Chapter 9, Fire Protection and Life Safety Systems:

(1)IFC, Chapter 9, Section 901.4.7, Pump and riser room size, is deleted and replaced with the following: "901.4.7 Pump and Riser Room Size. 901.4.7.1 Fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all installed equipment necessary for the installation and to provide sufficient working room around the stationary equipment. Clearances around equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly and not less than the following mi

Free access — add to your briefcase to read the full text and ask questions with AI

Legislative History

Amended by Chapter 95, 2023 General Session

Nearby Sections

15
View on official source ↗

Cite This Page — Counsel Stack

Bluebook (online)
Utah § 15A-5-204, Counsel Stack Legal Research, https://law.counselstack.com/statute/ut/15A-5-204.