§ 791.014 — MINIMUM SPECIFICATIONS FOR INTERIOR FIRE ESCAPES.

Texas § 791.014
JurisdictionTexas
Code HSHealth and Safety Code

This text of Texas § 791.014 (MINIMUM SPECIFICATIONS FOR INTERIOR FIRE ESCAPES.) is published on Counsel Stack Legal Research, covering Texas primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Tex. Health and Safety Code Code Ann. § 791.014 (2026).

Text

Sec. 791.014. MINIMUM SPECIFICATIONS FOR INTERIOR FIRE ESCAPES.

(a)An interior fire escape may be:
(1)a stairway composed of iron, steel, or concrete; or
(2)a straight or spiral chute composed of iron or steel.
(b)The fire escape must be enclosed with a noncombustible material. All door and window openings in the enclosure must be protected with self-closing fireproof shutters.
(c)Balconies or landings used with an interior fire escape must meet the construction requirements imposed under Section 791.012 , except that a balcony used with an interior fire escape must permit at least 40 inches of unobstructed passageway, and the balconies or landings must be located on a level with the floors of the building.
(d)The stairs of an interior stairway fire escape must meet the requirements

Free access — add to your briefcase to read the full text and ask questions with AI

Legislative History

Acts 1989, 71st Leg., ch. 678, Sec. 1, eff. Sept. 1, 1989.