South Dakota Statutes
§ 34-38-30 — Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.
No person may dispense fuel from an aboveground storage tank by either gravity flow or pressurization of the tank. The owner of an aboveground storage tank shall prevent the release of liquid from the tank by syphon flow. If an aboveground storage tank is at an elevation that produces a gravity head on the dispensing device, the tank outlet shall be equipped with a device such as a normally - closed solenoid valve that will prevent gravity flow from the tank to the dispenser. This device shall be located adjacent to and downstream of the outlet valve. The device shall be installed and adjusted so that liquid cannot flow by gravity from the tank to the dispenser if the piping or hose fails. If a submersible pump system is used, a listed rigidly anchored emergency shutoff valve, incorporatin
Free access — add to your briefcase to read the full text and ask questions with AI
South Dakota § 34-38-30 (Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.) — published by Counsel Stack Legal Research, free access to 12M+ legal documents.
Legislative History
SL 1991, ch 269, § 8.
Nearby Sections
15
§ 34-1-1
§ 34-1-1§ 34-1-1.1
Department reorganized and continued.§ 34-1-15
§ 34-1-15§ 34-1-19
Repealed§ 34-1-2
, 34-1-2.1