Text

A.A person shall not install an underground storage tank unless the underground storage tank meets all of the following requirements:
1.It is designed to prevent releases due to corrosion or structural failure for the operational life of the tank.
2.It is cathodically protected against corrosion, constructed of noncorrosive material, steel clad with a noncorrosive material or designed in a manner to prevent the release of a regulated substance.
3.The material used in the construction or lining of the tank is compatible with the substance to be stored.
B.A person shall not install an underground storage tank unless the underground storage tank meets the secondary containment performance standards for new underground storage tank systems prescribed in 40 Code of Federal Regulations