[This opinion has been published in Ohio Official Reports at 85 Ohio St.3d 275.]

THE STATE EX REL. DIBBLE, APPELLANT, v. PRESRITE CORPORATION ET AL., APPELLEES. [Cite as State ex rel. Dibble v. Presrite Corp., 1999-Ohio-263.] Workers’ compensation—Alleged violation of specific safety requirement dealing with insulated personal protective gear—VSSR application denied by Industrial Commission—Cause returned to commission for further consideration and amended order, when. (No. 96-2166—Submitted January 26, 1999—Decided April 7, 1999.) APPEAL from the Court of Appeals for Franklin County, No. 95APD10-1273. __________________ {¶ 1} Appellee Presrite Corporation is a metal fabricator. The plant’s induction heating units anchor the manufacturing process, heating the steel out of which metal forgings are made. An induction heating failure stops that assembly process. {¶ 2} On August 7, 1990, an induction heater kept shutting down. Appellant-claimant, Gary G. Dibble, Sr., Presrite’s maintenance electrician, suspected that a 2,000-kilowatt transformer on the mezzanine level of the plant was overheating. Claimant went to investigate, with the intention of checking the transformer cooling hoses for temperature and flow. {¶ 3} The transformer converted an incoming potential of 4,160 volts into a lower voltage suitable for plant use. The transformer was housed in a walk-in cabinet with east and west doors. The east double doors accessed the transformer’s high-voltage side and were protected by a mechanical interlock. The interlock acted as a power lockout device and roughly consisted of a knife switch, a knife switch lock, a door dead-bolt lock, and a single “kirk” key that accessed both locks. To enter the cabinet, the adjacent knife switch was opened (pulled down), which SUPREME COURT OF OHIO

shut down power to the transformer. Then the knife switch lock — located on the switch’s handle — was turned to the locked position. Only then could the kirk key be removed from the handle and inserted into the door dead bolt, thus opening the doors. There was also a remote main power location from which the power could be disconnected, but testimony indicates that even when using the main disconnect, the knife switch still had to be locked down in order to remove the kirk key that was necessary for the remaining dead bolt. {¶ 4} Despite the interlock, claimant, on the date of injury, was able to enter the cabinet while the power was still on. Claimant knew that the transformer was energized. He did not know that the cooling hoses were attached to the transformer with copper connectors, and, as a result, claimant was severely injured when his hand brushed against one of them. {¶ 5} Sometime later, in addition to the kirk key still in the knife switch, a second kirk key was discovered in the door dead bolt. This meant that the cabinet could be opened without cutting power at the knife switch. The second key was immediately destroyed by maintenance supervisor Jerry Westfall. {¶ 6} After a workers’ compensation claim was allowed by appellee Industrial Commission of Ohio, claimant sought additional compensation, alleging that Presrite had violated certain specific safety requirements (“VSSR”) dealing with insulated personal protective gear. At hearing, claimant testified that, on the date of injury, the cabinet doors were propped open with the unit running when he arrived at the transformer site. Claimant said that he had seen the doors propped open with the unit energized several times in the four to six weeks preceding the accident, which corresponded to a period of frequent transformer overheating. Claimant did not know who was propping the doors open, but stated that Presrite knew of—and condoned—the practice. According to claimant, Westfall told him that the open doors provided ventilation that helped cool the unit.

2 January Term, 1999

{¶ 7} Claimant stated that he could not disconnect the power at the knife switch before entering because it was broken. According to claimant, a broken spring mechanism prevented the knife switch from opening as quickly as it should, creating the risk of an arc-over explosion. Claimant reported that the knife switch had been broken for two to three months prior to the accident and that his repeated complaints to Presrite had been ignored. Claimant stated that had the knife switch been working properly, he definitely would have used it. Claimant testified that the coolant pump was on a separate circuit from that of the transformer. He could, therefore, check the hoses with the transformer off. {¶ 8} When questioned as to why he did not instead go to the main power disconnect, claimant stated that he could not accurately gauge hose flow and particularly temperature unless he was able to access the hoses immediately after the unit was deenergized. This eliminated going to the main switch room to deenergize the unit, which was an eight-to-ten-minute process. {¶ 9} Claimant denied knowledge of a second key. He also stated that he did not notice whether a second kirk key was in the door because the door was already open. He did add, however, that a second kirk key was not the only way to circumvent the interlock. He stated that once a single key had been properly used to open the doors, the doors could be propped open, the key reinserted into the knife switch, and the power reactivated. {¶ 10} Claimant finally testified that he had seen Presrite safety coordinator, Walle (or Wally) Woodworth, among others, work around energized transformers. {¶ 11} Presrite presented several employees to rebut claimant’s testimony. Witnesses denied having ever seen the east side doors open with the power on. Westfall also specifically denied the remarks attributed to him. Witnesses denied that Presrite required or allowed anyone to work on energized equipment. Presrite

3 SUPREME COURT OF OHIO

employees denied having seen anyone work on a live high-voltage transformer, and Woodworth specifically denied doing so. {¶ 12} Certain employees denied that the knife switch was broken. However, on cross-examination, Woodworth admitted that while the knife switch itself was functioning properly, the spring mechanism that controlled it had had problems before the accident. Follow-up questioning and testimony, however, never elicited whether the problem was indeed recurrent or whether it had been resolved before the accident. {¶ 13} Everyone denied awareness of a second kirk key prior to its discovery in the dead-bolt lock after claimant’s accident. All witnesses additionally denied having ever seen or heard of the claimant’s having a second key. {¶ 14} A commission hearing officer concluded that a second kirk key was the only way to override the interlock — rejecting claimant’s alternate theory for lack of corroborative evidence. The hearing officer also found that Presrite did not know of or authorize the second kirk key. In the same vein, he found insufficient evidence to attribute the key to the claimant. Based on these findings, the hearing officer reasoned: “[A]s designed and installed[,] it was mechanically impossible to gain access to the transformer while it was energized. It is therefore found that claimant was not required to work in proximity to energized lines * * * [and Ohio Adm.Code] 4121:1-5-17(I)(4) is held not to be applicable.” {¶ 15} Similar logic was used to determine that the transformer’s power source was isolated so as to render Ohio Adm.Code 4121:1-5-23(A) inapplicable. {¶ 16} In denying claimant’s motion for reconsideration, a staff hearing officer wrote: “The Hearing Officer’s conclusion that the claimant was not required to work in proximity to energized lines is not found to be a mistake of fact.

4 January Term, 1999

Free access — add to your briefcase to read the full text and ask questions with AI

Related

State Ex Rel. Johnson v. Indus. Comm., 07ap-503 (5-20-2008)
2008 Ohio 2421 (Ohio Court of Appeals, 2008)

Cite This Page — Counsel Stack

Bluebook (online)
1999 Ohio 263, 85 Ohio St. 3d 275, Counsel Stack Legal Research, https://law.counselstack.com/opinion/state-ex-rel-dibble-v-presrite-corp-ohio-1999.