Star Varifoam Corp. of America v. Buffalo Reinsurance Co.

307 S.E.2d 194, 64 N.C. App. 306, 1983 N.C. App. LEXIS 3262
CourtCourt of Appeals of North Carolina
DecidedOctober 4, 1983
DocketNo. 8222SC850
StatusPublished
Cited by1 cases

This text of 307 S.E.2d 194 (Star Varifoam Corp. of America v. Buffalo Reinsurance Co.) is published on Counsel Stack Legal Research, covering Court of Appeals of North Carolina primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Star Varifoam Corp. of America v. Buffalo Reinsurance Co., 307 S.E.2d 194, 64 N.C. App. 306, 1983 N.C. App. LEXIS 3262 (N.C. Ct. App. 1983).

Opinion

JOHNSON, Judge.

Plaintiff assigns as error the court’s granting of summary-judgment for defendant. Rule 56(c) of the North Carolina Rules of Civil Procedure provides that summary judgment will be granted “if the pleadings, depositions, answers to interrogatories, and admissions on file, together with the affidavits, if any, show that there is no genuine issue as to any material fact and that any party is entitled to judgment as a matter of law.” An issue is genuine if it “may be maintained by substantial evidence.” City of Thomasville v. Lease-Afex, Inc., 300 N.C. 651, 268 S.E. 2d 190 (1980); Kessing v. Mortgage Corp., 278 N.C. 523, 180 S.E. 2d 823 (1971).

Defendant claims plaintiff forfeited its right to recovery under the insurance policy by violating certain of its conditions. A breach of a policy condition bars any recovery under the policy. As stated in Couch on Insurance, Vol. 7, § 36:53 (2d ed. 1961):

The acceptance by the insured of a policy which includes conditions imposes upon him the duty of complying therewith, and failure so to do releases the insurer from liability in the absence of a contrary contract provision, or a waiver or estoppel.

Furthermore, G.S. 58-176, prescribes the printed form of a policy of fire insurance, the “Standard Fire Insurance Policy of the State of North Carolina.” G.S. 58-176(b) provides as follows:

No policy or contract of fire insurance except contracts of automobile fire, theft, comprehensive and collision, marine and inland marine insurance shall be made, issued or delivered by any insurer or by any agent or representative thereof, on any property in this State, unless it conforms in substance with all of the provisions, stipulations, agreements and conditions, of the policy form in subsection (c) of this section.

[309]*309Thus, the statutory Standard Fire Insurance Policy is incorporated into every policy of fire insurance issued in North Carolina. Boyd v. Insurance Co., 245 N.C. 503, 96 S.E. 2d 703 (1957); Glover v. Insurance Co., 228 N.C. 195, 45 S.E. 2d 45 (1947).

The Standard Fire Insurance Policy specifically provides that no suit or action on the policy for the recovery of any claim may be maintained unless all the requirements of the policy have been met. G.S. 58476(c). Therefore, the question here is whether there is a genuine issue of fact as to compliance by plaintiff with all of the conditions of the policy. If plaintiff violated any one of the conditions, then recovery is barred, and summary judgment for defendant is proper.

One of the policy conditions which plaintiff allegedly violated is the protection maintenance provision. It states:

Protection Maintenance: It is agreed that the whole of the protections provided for the safety of the insured property shall be maintained in good order throughout the currency of this Certificate and shall be in use at all times out of business hours or when the Insured’s premises are left unattended, and that such protection shall not be withdrawn or varied to the detriment of the interests of the Underwriters without their consent.

Defendant claims plaintiff failed to maintain in good order the fire protection or sprinkler system at the Star building thus violating this provision. It is not contested that the sprinkler system is one of the fire protections referred to in the provision.

The evidence presented as to this alleged violation may be summarized as follows: The sprinkler system at the Star building was supplied with water from an open pond or cistern located on the premises which was pumped into an elevated 50,000 gallon gravity tank. The tank, in turn, supplied water to the actual sprinkler heads located throughout the building. Philip Olshinski, a fire investigator, stated in his affidavit that as part of his investigation on the day of the fire, he was present when the elevated steel gravity tank that supplied water to the sprinkler system was inspected. According to Olshinski, at the time of the inspection, the outside stem and yoke valve that controlled water flowing into the sprinkler system from the tank was closed, mak[310]*310ing it impossible for water to flow into the sprinkler system. Moreover, when the investigators opened the valve, the steel gravity tank contained no water.

M. T. Channey, who was employed by plaintiff from the time it moved into the Star building until the fire, testified that he was at one time responsible for filling the 50,000 gallon tank with water. Channey said it was necessary to refill the tank often because there was a leak in an underground pipe. The leak was of such size that it allowed all the water to drain from the 50,000 gallon tank in approximately two days, and the leak appeared to be getting larger. Channey pointed out the leak and the need to repair it to Morris Herron and Melvin Peed, who are two of plaintiffs shareholders and part owners of the Star building, who said they would fix it later when they got caught up. Channey estimated that the last time he filled the water tank was about a month or two before the fire.

In addition, defendant presented the affidavit of Charles R. Manning who was hired by defendant to conduct tests on the sprinkler system. Manning conducted a thorough study of the sprinkler system and tested it to determine if it was in operation, or was even operational at the time of the fire. He performed a leak rate test on the sprinkler system which showed that 10 gallons of water per minute were being lost out of the system at 15 pounds per square inch system pressure. Three leaks were located and after extensive excavation, a crack and leak in the main sprinkler line was discovered. After removing a section of the pipe containing the crack and studying it, Manning determined the crack was quite old. Due to the placement of the pipe under approximately four and one-half feet of ground, and the fact the pipe was protected by poured concrete pads, Manning expressed the opinion that the pipe had not been damaged either during or after the fire. Manning stated that at normal system pressure, the cracked pipe would result in the water tower being emptied in three days or less. Finally, based on his study and tests, Manning concluded that “the sprinkler system could not have been, and indeed was not, operable at the time of the fire that occurred on April 2, 1980.”

Plaintiff argues that the evidence concerning the maintenance of the sprinkler system is not conclusive and relies upon [311]*311the affidavit of its expert, James Samuel McKnight. At plaintiffs request, McKnight observed the tests performed on the sprinkler system by Mr. Manning so as to determine whether the tests were conducted fairly and whether any conclusions reached were supported fully by the test results. In his affidavit, McKnight stated that the bituminous coating on the surface of the pipe at the location of the crack was inadequate to protect the pipe from corrosion, that it appeared corrosion had been occurring for a considerable length of time, and that the crack was old. He said the crack was probably caused by differential settling of the foundations of the boiler house and the warehouse and was accelerated by the inadequate coating on the exterior of the pipe. In his opinion, the water could have leaked out of the storage tank through a crack in the underground pipe.

Mr.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Bentley v. North Carolina Insurance Guaranty Ass'n
418 S.E.2d 705 (Court of Appeals of North Carolina, 1992)

Cite This Page — Counsel Stack

Bluebook (online)
307 S.E.2d 194, 64 N.C. App. 306, 1983 N.C. App. LEXIS 3262, Counsel Stack Legal Research, https://law.counselstack.com/opinion/star-varifoam-corp-of-america-v-buffalo-reinsurance-co-ncctapp-1983.