Southeast Alabama Gas District v. Killingsworth

175 So. 2d 741, 278 Ala. 48, 1965 Ala. LEXIS 841
CourtSupreme Court of Alabama
DecidedFebruary 18, 1965
Docket4 Div. 210
StatusPublished
Cited by2 cases

This text of 175 So. 2d 741 (Southeast Alabama Gas District v. Killingsworth) is published on Counsel Stack Legal Research, covering Supreme Court of Alabama primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Southeast Alabama Gas District v. Killingsworth, 175 So. 2d 741, 278 Ala. 48, 1965 Ala. LEXIS 841 (Ala. 1965).

Opinions

PER CURIAM.

Appellee recovered judgment in the circuit court of Pike County on a complaint which reads as follows:

“Plaintiff claims of defendants $4,-000.00 for that on, to-wit, March 6, 1962, defendants installed a Limit Control upon a combination air conditioning unit and furnace in Plaintiff’s office and clinic building at Brundidge, Pike County, Alabama, Defendants were negligent in and about the installation of said Limit Control and, as a proximate result of said negligence, the air conditioning unit and furnace became overheated and plaintiff’s building and furnishings therein were burned and rendered less valuable.”

It is to be noted that the negligence charged to defendants arises out of the installation of the Limit Control; that as a proximate result of said alleged negligence two incidents happened, namely, (a) the air conditioning unit and furnace became overheated; (b) plaintiff’s building and the furnishings therein were burned and rendered less valuable.

It appears from the evidence that plaintiff was a practicing physician at the time of the fire and since said time; that he owned and operated a clinic in Brundidge, Alabama, for the reception, examination and treatment of patients; that the clinic was the subject of the fire.

This building or clinic when it caught fire was heated with a gas furnace situated in a furnace room that adjoined a laboratory, all in the same building or clinic. It further appears that the heating apparatus was not properly functioning so as to adequately heat the rooms or building.

The defendant, Southeast Alabama Gas District, supplied the natural gas consumed in the heater or furnace to heat the air, while the defendant George F. Wheelock Company sold equipment used in heating systems or installations operated by burning gas.

One Mr. Senn, an agent or servant of the defendant Southeast Alabama Gas District, and a Mr. George F. Wheelock, a sales representative of defendant Wheelock Company, responding to the complaint of plaintiff that his heating facilities in the clinic were not functioning properly, met at the clinic about 11:00 o’clock A.M., and forthwith proceeded to inspect and examine the system, or parts of it, to ascertain the cause of the heat deficiency in the building. No question is here raised as to their authority to act for and represent the defendants as they did.

Following their joint inspections and examinations of the facilities, they concluded that the blower on the bottom of the heater underneath the heat exchange was hanging by one bolt and that the fan used to blow the heated air into the ducts that ramified the building was loose. They proceeded to correct these defects. They also concluded that the limit control switch was not functioning properly and was cutting the heat off too quickly to warm the several offices [50]*50in the building to a degree preset by the thermostat control located at a strategic point in the building.

They proceeded to remove the existing limit control switch and install a new one, which is conceded to have been tested and found to be functioning properly, or at least that statement appears in the record before us.

After observing the operation of the heater for a few minutes and being impressed that the furnace or heater supplying the heat for the building was and would function properly and would supply adequate heat, they left the clinic about noon with the furnace or heater burning.

Plaintiff and his wife left the clinic about 12:30 P.M. following the departure of the technicians, Mr. Senn and Mr. Wheelock, and went to lunch, where in about 30 minutes after their departure they received a call informing them that the clinic was on fire. They left immediately for the office.

The heater or furnace was a mechanical device that burned natural gas in a chamber. This particular heater'would perform by air blowing over a metal box in which the fire is located. A thermostat located in the building would cut the gas off and on when the heated building would reach a preset temperature, that is, 'when functioning properly.

The limit control switch was a safety device that was designed to cut off the main flames of gas in the heater or furnace when the heat reached a preset temperature designated by the control switch. When the heat, dispersed through' the building for warmth, reached a preset temperature at which the thermostat was fixed, then the thermostat was designed to shut off the heating flames in the furnace, while the limit control switch was designed also to shut off the heating flames in the furnace should the thermostat fail to function to that end. The limit control switch was an additional device to prevent the furnace or heater from overheating.

It is without dispute that the new limit control device that was put in the heater the day of the fire was wired incorrectly at first by Mr. Senn and Mr. Wheelock, but was again rewired, according to the evidence of Mr. Wheelock, in accordance with a diagram furnished with the apparatus. These two witnesses, Mr. Senn and Mr. Wheelock, who assumed the installation of the new limit control switch, both testified that in their opinion the switch was correctly wired to function.

A Mr. Johnson, a witness for the plaintiff, whose experience was adduced by evidence before the jury, testified that; during the afternoon following the fire, he saw the switch and that it was not correctly wired so that it would properly function.

There is no evidence that prior to the departure from the clinic of Mr. Senn and Mr. Wheelock, and of the plaintiff and his wife, there was any uncontrolled fire in the furnace room or the adjoining laboratory.

' There was evidence as to the location of the uncontrolled flames after their discovery, and also as to the charred'condition of the furnace room and of the laboratory adjacent thereto.

The fire chief testified that after the fire cooled down, he found some charred 2 x 4’s where the duct work went through the wall; that the wall above the heater was burned, but nothing lower down was burned; that there was fire in a lot of different places that had to be put out. This was about 1:00 o’clock P.M. Where the wiring came through, the wall, at the location of the electric fuses, was either burned or charred. This witness never did examine the heater.

Counsel for plaintiff during the trial stated to the jury:

“It is agreed that the defendants on the date of the fire removed the limit control and installed this one in the furnace, (indicating) This has been tested by a reputable testing laboratory and so far as the device is concerned, it has no defect.”

[51]*51The following testimony was adduced:

(Mr. Johnson, testifying as a witness for plaintiff)
“Q. Tell the jury where this limit control is situated on the gas furnace?
“A. It is located in the top of the heater, in the top of the furnace.
“Q. That is where the hot air leaves the furnace ?
“A. Where it picks up heat from the furnace should it over heat.
“Q. That is generally the hottest part, where the air is the hottest?
“A. Right.
“Q. What is the purpose of this limit control?
“A.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Ex Parte Jett
5 So. 3d 640 (Supreme Court of Alabama, 2007)
Johnson v. Knight
459 F. Supp. 962 (N.D. Mississippi, 1978)

Cite This Page — Counsel Stack

Bluebook (online)
175 So. 2d 741, 278 Ala. 48, 1965 Ala. LEXIS 841, Counsel Stack Legal Research, https://law.counselstack.com/opinion/southeast-alabama-gas-district-v-killingsworth-ala-1965.