30 CFR · Mineral Resources
§ 75.1107-16 — Inspection of fire suppression devices.
eCFR · current through Sep 10, 2026
§ 75.1107-16 Inspection of fire suppression devices.
(a)All fire suppression devices shall be visually inspected at least once each week by a person qualified to make such inspections.
(b)Each fire suppression device shall be tested and maintained in accordance with the requirements specified in the appropriate National Fire Code listed as follows for the type and kind of device used:
National Fire Code No. 11A “High Expansion Foam Systems” (NFPA No. 11A—1970).
National Fire Code No. 13A “Care and Maintenance of Sprinkler Systems” (NFPA No. 13A—1971).
National Fire Code No. 15 “Water Spray Fixed Systems for Fire Protection” (NFPA No. 15—1969).
National Fire Code No. 17 “Dry Chemical Extinguishing Systems” (NFPA No. 17—1969).
National Fire Code No. 72A “Local Protective Signaling Sy
Free access — add to your briefcase to read the full text and ask questions with AI
30 C.F.R. § 75.1107-16 (Inspection of fire suppression devices.) — published by Counsel Stack Legal Research, free access to 12M+ legal documents.
Nearby Sections
11
§ 75.1107-12
Inerting of mine atmosphere prohibited.§ 75.1107-13
Approval of other fire suppression devices.§ 75.1107-16
Inspection of fire suppression devices.§ 75.1108
Approved conveyor belts.§ 75.1200
Mine map.§ 75.1200-1
Additional information on mine map.§ 75.1200-2
Accuracy and scale of mine maps.