§ 75.1101-14 Installation of dry powder chemical systems.
(a)Self-contained dry powder chemical systems shall be installed to protect each belt-drive, belt takeup, electrical-controls, gear reducing units and 50 feet of fire-resistant belt or 150 feet of non-fire-resistant belt adjacent to the belt drive.
(b)The fire-control components of each dry powder chemical system shall be a type approved by the Underwriters' Laboratories, Inc., or Factory Mutual Engineering Corp.
(c)The components of each dry powder chemical system shall be located so as to minimize the possibility of damage by roof fall or by the moving belt and its load.
Free access — add to your briefcase to read the full text and ask questions with AI
Nearby Sections
11
§ 75.1101-9
Back-up water system.§ 75.1101-11
Inspection of water sprinkler systems.§ 75.1101-12
Equivalent dry-pipe system.§ 75.1101-13
Dry powder chemical systems; general.§ 75.1101-14
Installation of dry powder chemical systems.§ 75.1101-15
Construction of dry powder chemical systems.§ 75.1101-17
Sealing of dry powder chemical systems.§ 75.1101-18
Dry powder requirements.§ 75.1101-19
Nozzles; flow rate and direction.Cite This Page — Counsel Stack
Bluebook (online)
30 C.F.R. § 75.1101-14, Counsel Stack Legal Research, https://law.counselstack.com/cfr/30/75/75.1101-14.