FEDERAL · 30 U.S.C. · Chapter 22

Trolley wires and trolley feeder wires

Current through Pub. L. 119-102
Title 30Mineral Lands and Mining·Ch. 22 — MINE SAFETY AND HEALTH·Subch. III
(a)Intervals for cutoff switches Trolley wires and trolley feeder wires shall be provided with cutout switches at intervals of not more than 2,000 feet and near the beginning of all branch lines.
(b)Overcurrent protection devices Trolley wires and trolley feeder wires shall be provided with overcurrent protection.
(c)Location of wires Trolley wires and trolley feeder wires, high-voltage cables and transformers shall not be located inby the last open crosscut and shall be kept at least 150 feet from pillar workings.
(d)Adequate insulation and guard devices; promulgation of safety guidelines Trolley wires, trolley feeder wires, and bare signal wires shall be insulated adequately where they pass through doors and stoppings, and where they cross other power wires and cables. Trolley wires