Washington Statutes

§ 19.27.710 — Owners of buildings equipped with fire dampers, smoke dampers, combination fire and smoke dampers, or smoke control systems—Duties—Penalty.

Washington § 19.27.710
JurisdictionWashington
Title 19BUSINESS REGULATIONS—MISCELLANEOUS
Ch. 19.27STATE BUILDING CODE

This text of Washington § 19.27.710 (Owners of buildings equipped with fire dampers, smoke dampers, combination fire and smoke dampers, or smoke control systems—Duties—Penalty.) is published on Counsel Stack Legal Research, covering Washington primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Wash. Rev. Code § 19.27.710 (2026).

Text

(1)At a minimum, owners of buildings equipped with fire dampers, smoke dampers, combination fire and smoke dampers, or smoke control systems must:
(a)Have all newly installed fire dampers, smoke dampers, combination fire and smoke dampers, and smoke control systems tested and inspected within twelve months of installation;
(b)Have all fire dampers, smoke dampers, and combination fire and smoke dampers tested and inspected at least once every four years, or every six years for hospitals, regardless of the date of initial installation; and
(c)Have all smoke control systems tested and inspected at least once every six to twelve months, as required by the applicable national fire protection association standard.
(2)All owners of buildings subject to chapter 88, Laws of 2020 must maint

Free access — add to your briefcase to read the full text and ask questions with AI

Related

§ 19.27.740
Washington § 19.27.740
§ 19.27.700
Washington § 19.27.700

Legislative History

[2020 c 88 s 2.]