This text of Texas § 214.301 (PERMITTED REGULATION OF APARTMENT BUILDING STAIRWAY REQUIREMENTS.) is published on Counsel Stack Legal Research, covering Texas primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Tex. Local Government Code Code Ann. § 214.301 (2026).

Text

Sec. 214.301. PERMITTED REGULATION OF APARTMENT BUILDING STAIRWAY REQUIREMENTS.

(a)A municipality may exercise the authority under this section regardless of whether the municipality has adopted local amendments to the International Building Code under Section 214.216 (c).
(b)A municipality may authorize an apartment building to have a single stairway only if the building:
(1)does not have more than six stories above grade plane and is not a high-rise as defined by the International Building Code, as adopted under Section 214.216 ;
(2)does not have more than four dwelling units on any floor;
(3)has automatic sprinkler locations in each interior exit stairway, regardless of the type of stairway construction, that comply with the requirements prescribed by National Fire Protection Assoc

Free access — add to your briefcase to read the full text and ask questions with AI

Legislative History

Added by Acts 2025, 89th Leg., R.S., Ch. 701 (S.B. 2835 ), Sec. 1, eff. September 1, 2025.