§ 40-10-250 — Fire Protection Sprinkler System Specification Sheet; completion of form; attachment to building permit applications.
(A)A "Fire Protection Sprinkler System Specification Sheet" must be completed for every fire protection sprinkler system, and submitted on a form approved by the State Fire Marshal's Office to the authority having jurisdiction. The completed form must contain the following information at a minimum:
(1)the available static and residual water pressure from a flow test conducted less than one year before submittal;
(2)the volume per minute of the available water flow and duration;
(3)the source of water supply;
(4)the NFPA hazard classifications and details of storage arrangement, if applicable;
(5)the occupancy use of the building, or the area to be sprinkled;
(6)the type of system to be installed;
(7)the applicable National Fire Protection Association standards to be followed for ea