Text
(1)The refrigeration system of a refrigerated locker plant shall be equipped with accurate controls for the maintenance of uniform temperatures as required in this section in the various refrigerated rooms of such plant and shall be of adequate capacity to provide under extreme conditions of outside temperatures and under peak load conditions in the normal operation of such plant, the following temperatures in the following rooms respectively:
(a)Chill room temperature shall be within four degrees Fahrenheit plus or minus of 36 degrees above zero Fahrenheit, with a tolerance of 10 degrees Fahrenheit for 24 hours after fresh food is put in such room for chilling.
(b)In all locker plants operating on July 5, 1947, the locker room temperature shall not exceed 12 degrees Fahrenheit plus. In