Oregon Statutes

§ 628.300 — Maintaining uniform temperatures; records

Oregon § 628.300
JurisdictionOregon
Vol.15
Title 49Food and Other Commodities
Ch. 628Refrigerated Locker Plants

This text of Oregon § 628.300 (Maintaining uniform temperatures; records) is published on Counsel Stack Legal Research, covering Oregon primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Or. Rev. Stat. § 628.300 (2026).

Text

(1)The refrigeration system of a refrigerated locker plant shall be equipped with accurate controls for the maintenance of uniform temperatures as required in this section in the various refrigerated rooms of such plant and shall be of adequate capacity to provide under extreme conditions of outside temperatures and under peak load conditions in the normal operation of such plant, the following temperatures in the following rooms respectively:
(a)Chill room temperature shall be within four degrees Fahrenheit plus or minus of 36 degrees above zero Fahrenheit, with a tolerance of 10 degrees Fahrenheit for 24 hours after fresh food is put in such room for chilling.
(b)In all locker plants operating on July 5, 1947, the locker room temperature shall not exceed 12 degrees Fahrenheit plus. In

Free access — add to your briefcase to read the full text and ask questions with AI

Nearby Sections

15
View on official source ↗

Cite This Page — Counsel Stack

Bluebook (online)
Oregon § 628.300, Counsel Stack Legal Research, https://law.counselstack.com/statute/or/628.300.