Maryland Statutes

§ 9-403

Maryland § 9-403
JurisdictionMaryland
Article gpsPublic Safety
Title9

This text of Maryland § 9-403 is published on Counsel Stack Legal Research, covering Maryland primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Md. Code Ann., Public Safety § 9-403 (2026).

Text

(a)Each high–rise building constructed after July 1, 1974, shall be protected by a complete automatic sprinkler system installed in accordance with accepted engineering practices as approved by the authority with jurisdiction.
(b)(1) This section does not apply to a building that is less than 75 feet in height above grade level if:
(i)the local fire department has at least one approved first line piece of aerial equipment that is capable of reaching the roof of the building; and
(ii)accessibility to the building is provided on two sides of the perimeter of the building by a public way that is: 1. kept accessible at all times to the local fire department; and 2. close enough to the building to allow th

Free access — add to your briefcase to read the full text and ask questions with AI

Nearby Sections

15
§ 9-1001
§ 9-1001
§ 9-101
§ 9-101
§ 9-102
§ 9-102
§ 9-103
§ 9-103
§ 9-104
§ 9-104
§ 9-105
§ 9-105
§ 9-106
§ 9-106
§ 9-106.1
§ 9-106.1
§ 9-107
§ 9-107
§ 9-108
§ 9-108
§ 9-109
§ 9-109
§ 9-201
§ 9-201
§ 9-202
§ 9-202
§ 9-203
§ 9-203
§ 9-204
§ 9-204
View on official source ↗

Cite This Page — Counsel Stack

Bluebook (online)
Maryland § 9-403, Counsel Stack Legal Research, https://law.counselstack.com/statute/md/gps/9-403.