§ 9-403

Maryland·Article gps Public Safety·Title 9
(a)Each high–rise building constructed after July 1, 1974, shall be protected by a complete automatic sprinkler system installed in accordance with accepted engineering practices as approved by the authority with jurisdiction.
(b)(1) This section does not apply to a building that is less than 75 feet in height above grade level if:
(i)the local fire department has at least one approved first line piece of aerial equipment that is capable of reaching the roof of the building; and
(ii)accessibility to the building is provided on two sides of the perimeter of the building by a public way that is: 1. kept accessible at all times to the local fire department; and 2. close enough to the building to allow th