Text

Section 39. The air tank or other receptacle shall be prepared for internal inspection by the owner or user. The inspection plugs, handhole plates and manhole plates if provided shall be removed. The interior shall be cleaned of rust, scale, oil sludge and any other deleterious material. Ultrasonic thickness determination shall be permitted in lieu of, or in conjunction with, internal inspection for air tanks or other receptacles of 36 inches diameter or less. Thickness measurements shall be made in at least 8 areas: 2 on each head and 2 on both the top and bottom portions of the shell. Thickness determinations indicating significant reduction in material thickness over a general area shall be shown on the inspection report, as well as calculations for the reduction in allowable working pr