§ 553.9065 — Thermal efficiency standards for unvented attic and unvented enclosed rafter assemblies

Florida § 553.9065
JurisdictionFlorida
TitleXXXIII
Ch. 553BUILDING CONSTRUCTION STANDARDS

This text of Florida § 553.9065 (Thermal efficiency standards for unvented attic and unvented enclosed rafter assemblies) is published on Counsel Stack Legal Research, covering Florida primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Fla. Stat. § 553.9065 (2026).

Text

(1)Unvented attic and unvented enclosed rafter assemblies that are insulated and air sealed with a minimum of R-20 air-impermeable insulation meet the requirements of Section R402 of the Florida Building Code, 8th Edition (2023), Energy Conservation, if all of the following apply:
(a)The building has a blower door test result of less than 3 ACH50.
(b)The building has a positive input ventilation system or a balanced or hybrid whole-house mechanical ventilation system.
(c)If the insulation is installed below the roof deck and the exposed portion of roof rafters is not already covered by the R-20 air-impermeable insulation, the exposed portion of the roof rafters is insulated by a minimum of R-3 air-impermeable insulation unless directly covered by a finished ceiling. Roof rafters are no

Free access — add to your briefcase to read the full text and ask questions with AI

Legislative History

s. 7, ch. 2024-191.