Western States Fire Protection Co. of Alaska v. Municipality of Anchorage

146 P.3d 986, 2006 Alas. LEXIS 173, 2006 WL 3258233
CourtAlaska Supreme Court
DecidedNovember 9, 2006
DocketS-11895
StatusPublished
Cited by5 cases

This text of 146 P.3d 986 (Western States Fire Protection Co. of Alaska v. Municipality of Anchorage) is published on Counsel Stack Legal Research, covering Alaska Supreme Court primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Western States Fire Protection Co. of Alaska v. Municipality of Anchorage, 146 P.3d 986, 2006 Alas. LEXIS 173, 2006 WL 3258233 (Ala. 2006).

Opinion

OPINION

CARPENETI, Justice.

I. INTRODUCTION

More than one hundred acoustic tiles hang from the ceiling of the auditorium at A.J. Dimond High School in Anchorage. The acoustic tiles hang below the fire sprinklers. The fire department determined that the tiles obstructed too much water from the sprinklers. The board of building examiners, finding that the sprinkler installation complied with local fire codes, overruled the fire department. The superior court reversed the board's decision and the sprinkler installer now appeals. Because interpretation of the fire code calls for the board's technical expertise, we ask only whether the board's decision has a rational basis in law and fact. However, even under this deferential standard of review, we hold that the board failed to determine whether the sprinklers and the tiles in their current configuration actually permit adequate water coverage. We therefore vacate the decision of the board and remand the case to the board for reconsideration, which may include taking additional evidence.

II. FACTS AND PROCEEDINGS

Western States Fire Protection Company of Alaska (Western States) designed and installed the sprinkler system in the new "au-diteria" of A.J. Dimond High School. Overhead in the auditeria more than one hundred acoustic tiles, known as "clouds," hang ap *988 proximately twelve feet below the ceiling. Each of the clouds is four feet wide and eight to twelve feet long. Western States's technical drawings, which the Anchorage Fire Department preliminarily approved, show the positions of the clouds relative to the sprinklers. The parties disagree on the distance between the clouds. Western States asserts that the clouds "are spaced roughly two feet apart," referring to photographs of the au-diteria ceiling and technical drawings. However, based on the same drawings, the fire department asserts that the clouds are only six inches apart. 1 In any case, Western States conceded that the sprinklers and clouds are not configured to take advantage of the open gaps between the clouds. 2 After the clouds and sprinklers were installed, the fire department inspected the auditeria and issued a fire inspection notice expressing the department's concern over the number of clouds and their position below the sprinkler heads. According to the inspection notice, the clouds would disrupt the sprinkler discharge pattern, "resulting in inadequate coverage" of any fire erupting below the clouds. The fire marshal refused to approve the sprinklers until Western States remedied the situation by "remov[ing] obstructions and/or add{ing] additional sprinkler heads as necessary."

Western States appealed the fire department's decision to the Anchorage Board of Building Regulation Examiners and Appeals. 3 At hearings before the board, Western States pointed out that before construction it showed its sprinkler installation plans to five different entities Gneluding the fire marshal), who signaled their approval. According to Western States, because of the clouds, only sixty-eight percent of the "floor coverage is open to water application." Western States also indicated that the sprinklers are placed closer together than legally required, although the resulting additional water they provide would not make up for the water blocked by the clouds. Western States additionally noted that fire alarms and a nearby fire station provide backups for the sprinkler system. Although Western States was asked several questions about water flow and coverage during the hearing, it is unclear from the record whether the board reached any conclusion about the amount of water actually capable of reaching the floor from the sprinklers and whether the amount would provide adequate protection against fire hazards in the auditeria.

The fire department's fire inspector urged the board to find "that the sprinklers [should] be extended through or between the acoustic panels to a level that [will] extend the coverage to the area below, in other words, to the floor area below, which is where the hazard is." Otherwise, according to the inspector, the sprinkler system fails to comply with the National Fire Protection Association standard for sprinkler systems (NFPA 13) 4 as incorporated into Anchorage's fire code. 5 The fire department submitted a letter from the manufacturer of the acoustic clouds, which stated that similar installations, including one at a high school in Fairbanks, were required to include additional sprinklers either in the gaps between the clouds or penetrating the clouds themselves.

*989 In deliberations after the hearing, the board members discussed NFPA 18's four-foot benchmark for sprinkler obstructions in connection with the four-foot width of the acoustical tiles. 6 According to one board member, "over four feet is not the same thing as four feet or more, and this is pretty clear[,] it says over four feet." Following this comment, another board member made a motion to grant Western States's appeal, remarking, "That's our only option." The board then voted unanimously that Western States had complied with NFPA 18.

The fire department appealed the board's decision to the superior court. Anchorage Superior Court Judge Philip R. Volland reversed the board's decision, applying the substitution of judgment standard of review. According to the superior court, substitution of judgment was appropriate, since "[the interpretation of such non-technical terms as 'continuous," 'non-continuous,' 'fixed obstructions, and 'over four feet wide' ... does not involve agency expertise or broad policy formulations." The superior court determined that the board's literal interpretation of NFPA 18 produced an absurd result, since the sprinkler-cloud arrangement might technically comply with NFPA 183 while negating the standard's purpose, "which is to ensure that a sufficient amount of water from the sprinkler reaches the hazard." 7 Western States appeals.

III. STANDARD OF REVIEW

Where the superior court acts as an intermediate court of appeal from an administrative decision such as the board's, we review the administrative decision directly. 8 When the board's interpretation of law turns on its technical expertise or "the determination of fundamental policies within the seope of the [board's] statutory function," 9 we inquire whether the interpretation has a rational basis. As we stated in Tesoro Alaska Petroleum Co. v. Kenai Pipe Line Co., two cireumstances generally call for rational basis review: (1) "where the agency is making law by creating standards to be used in evaluating the case before it and future cases," and (2) "when a case requires resolution of policy questions which lie within the agency's area of expertise and are inseparable from the facts underlying the agency's decision." 10

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Apline Energy, LLC v. Matanuska Electric Association
369 P.3d 245 (Alaska Supreme Court, 2016)
Alaska Police Standards Council v. Parcell
348 P.3d 882 (Alaska Supreme Court, 2015)
State v. Jeffery
170 P.3d 226 (Alaska Supreme Court, 2007)

Cite This Page — Counsel Stack

Bluebook (online)
146 P.3d 986, 2006 Alas. LEXIS 173, 2006 WL 3258233, Counsel Stack Legal Research, https://law.counselstack.com/opinion/western-states-fire-protection-co-of-alaska-v-municipality-of-anchorage-alaska-2006.