This text of 78 N.E. 761 (Erickson v. American Steel & Wire Co. of New Jersey) is published on Counsel Stack Legal Research, covering Massachusetts Supreme Judicial Court primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
Erickson v. American Steel & Wire Co. of New Jersey, 78 N.E. 761, 193 Mass. 119, 1906 Mass. LEXIS 1165 (Mass. 1906).

Opinion

Rugg, J.

The fundamental question in these cases is, whether the defendant was negligent in the construction and maintenance of its steam power plant. The plaintiffs in the first and third cases and the plaintiff’s intestate in the second case were employees of the defendant working in a room adjoining the boiler room, in which a steam main burst, causing their injuries. Seventeen horizontal boilers were placed side by side in the boiler room. The steam main connecting with the boilers, including an expansion pipe on the end, was about one hundred forty-five feet long, with an inside diameter of fourteen inches and a thickness of one and one eighth inches to one and one fourth inches. The steam main was composed, outside of the expansion pipe, of seventeen headers, so called, made of cast iron, one for every boiler, each eight feet long with flanges on both ends, so that they could be bolted together, thus making a continuous steam main or pipe. Out of the lower side of each and connecting with it by a nozzle or T shaped piece, coming out of and forming a part of the header, was a six inch wrought iron pipe which, after making an angle, entered vertically its boiler. The dimensions of these headers were sufficient, if of cast iron, without flaw or defect, to sustain a steam pressure of one hundred twenty-five to one hundred fifty pounds to the square inch, with a factor of safety of twenty-one, which means that it would carry a pressure twenty-one times as great before breaking.

The line of headers which constituted the steam main was supported on brackets attached to brick piers. The headers [123]*123rested on rollers on the brackets, which permitted the steam main to move back and forth lengthwise on them, as it expanded with the heat. The expansion of the entire length was about three inches.

Between boilers ten and eleven there was a blank flange or cut-off so that boilers one to ten could be run at one pressure and eleven to seventeen at another pressure, and they were being so run at the time of the accident, although when the plant was first installed in 1896, the boilers which were first put in use were all run at the same pressure.

At the time of the accident, boilers one to ten were carrying one hundred fifty pounds of steam pressure and those numbered eleven to seventeen one hundred twenty-six pounds pressure. At the high pressure end the main was anchored through a brick wall with a nut and rod so that it could be tightened and stop the vibration. When tightened, it could not expand over half an inch at that end. At the other end of the steam main was a gooseneck, so called, which was a ten inch pipe sloping downward from the main for a considerable distance and then up again in another part of the building. This device permitted expansion at that end. There was no drip cock upon this gooseneck, but an elbow, designed to take return water and condensed steam back to the boilers. Upon the main steam line there was no expansion valve and there were no drip cocks.

The headers were purchased by the defendant at a reputable foundry, where they were tested, but the machine work upon the castings was done at the defendant’s shop and the steam main was put together and in place with its connections to the boilers by the defendant’s employees, and according to a design, both as to construction and connections, made by the defendant’s engineer. It was examined during construction by one Allen, who was a steam engineering inspector of wide experience, and in part was tested by him; and he approved it in most, if not all, respects. The defendant applied to the headers and the steam main the usual tests before the plant was put in use and made the customary inspection while the plant was in operation.

On the day of the accident, the header of boiler thirteen blew [124]*124out on the badk side opposite where the steam went in, leaving the main pipe in place and blowing out a space eighteen or twenty inches in length.

Examination showed that at the place of the break, the cast iron was spongy, stogy or porous, but this condition was concealed by a skin of good iron on the outside one sixteenth to one eighth of an inch in thickness and on the inside one fourth to one half an inch in thickness. The porous part did not show on the inside or outside of the pipe. At the defective place the good iron was between ■ one fourth and one half an inch thick which should bear over one thousand pounds pressure of steam.

There was evidence from several of the witnesses, whose familiarity with the construction and operation of steam plants was not in question, that the plan of this steam pipe line with its boiler connections and anchorage was defective. The professor of steam engineering at the Worcester Polytechnic Institute testified that it was not a mechanically proper construction, because sufficient arrangements were not provided for the expansion of the steam main, whereby there would be a tendency to weaken the joints throughout the length of the pipe, and that drip cocks along the line of the pipe were necessary, although none were provided, and that "cast iron was an unsuitable material of which to make the headers, because of its brittleness or rigidity, and that the method of connecting the feed pipes from the boilers to the main was improper. This testimony was supplemented in important particulars by another witness of acknowledged experience. The defendant invokes the rule applied in Fuller v. New York, New Haven, & Hartford Railroad, 175 Mass. 424, to the effect that it had performed its whole duty when it purchased the castings, out of which the main steam pipe was made, from a reputable manufacturer. One of these castings proved to be to some extent defective by reason of spongy metal, but this defective material was covered on both sides by good metal of a thickness sufficient, upon the undisputed evidence, to withstand a steam pressure of one thousand pounds, while it was being subjected at the time of the accident to only one hundred fifty pounds pressure. This evidence strongly points to some other cause for the accident than the defective casting. But this rule has no application to the facts here [125]*125disclosed, for the reason that the castings after being so purchased were finished by the defendant and were incorporated into a structure according to a design prepared by its own engineer, which, apart from any hidden defect in the castings, was asserted by the plaintiffs to have been defective in important particulars, which could have caused the break complained of.

The defendant stoutly contends that the employment of Allen to inspect the construction and his approval of it as a competent expert in such matters exonerates it from culpability. The defendant undertook, through its own agents, to design, manufacture and install its steam main and boiler connections. The castings for the headings, so far as appears, were the only materials purchased of other manufacturers. The defendant itself thus assumed to perform its general obligation of using proper care to provide safe machinery, appliances and apparatus for its. servants to work with. It cannot relieve itself from this responsibility by showing that it employed competent engineers to design and set up the appliances in question, or to inspect them after being in place. This is weighty evidence as tending to show that it took all the precaution which ordinary prudence required. Shrewsbury v. Smith, 12 Cush. 177. But the defendant must still bear its original responsibility of using due care to provide safe appliances.

Free access — add to your briefcase to read the full text and ask questions with AI

Related

Black v. Boston Consolidated Gas Co.
91 N.E.2d 192 (Massachusetts Supreme Judicial Court, 1950)
Mucha v. Northeastern Crushed Stone Co.
30 N.E.2d 870 (Massachusetts Supreme Judicial Court, 1940)
Noel v. Archidacono
192 N.E. 153 (Massachusetts Supreme Judicial Court, 1934)
Fraioli v. New York, New Haven & Hartford Railroad
190 N.E. 605 (Massachusetts Supreme Judicial Court, 1934)
Lamberti v. Neal
148 N.E. 463 (Massachusetts Supreme Judicial Court, 1925)
Roosen v. Peter Bent Brigham Hospital
235 Mass. 66 (Massachusetts Supreme Judicial Court, 1920)
Souden v. Fore River Ship Building Co.
112 N.E. 82 (Massachusetts Supreme Judicial Court, 1916)
Burk v. Hobart Mill & Elevator Co.
1915 OK 539 (Supreme Court of Oklahoma, 1915)
Maddox v. Ballard
105 N.E. 632 (Massachusetts Supreme Judicial Court, 1914)
White v. Newborg
94 N.E. 269 (Massachusetts Supreme Judicial Court, 1911)
Oakey v. Robb-Mumford Boiler Co.
88 N.E. 892 (Massachusetts Supreme Judicial Court, 1909)
Brooks v. Kinsley Iron & Machine Co.
88 N.E. 771 (Massachusetts Supreme Judicial Court, 1909)
West v. Linehan
87 N.E. 896 (Massachusetts Supreme Judicial Court, 1909)
Dulligan v. Barber Asphalt Paving Co.
87 N.E. 567 (Massachusetts Supreme Judicial Court, 1909)
Bowie v. Coffin Valve Co.
86 N.E. 914 (Massachusetts Supreme Judicial Court, 1909)

Cite This Page — Counsel Stack

Bluebook (online)
78 N.E. 761, 193 Mass. 119, 1906 Mass. LEXIS 1165, Counsel Stack Legal Research, https://law.counselstack.com/opinion/erickson-v-american-steel-wire-co-of-new-jersey-mass-1906.