30 CFR · Mineral Resources

§ 75.1107-10 — High expansion foam devices; minimum capacity.

30 CFR § 75.1107-10

This text of 30 C.F.R. § 75.1107-10 (High expansion foam devices; minimum capacity.) is published on Counsel Stack Legal Research, covering United States primary law. Counsel Stack provides free access to over 12 million legal documents including statutes, case law, regulations, and constitutions.

Bluebook
30 C.F.R. § 75.1107-10 (2026).

Text

§ 75.1107-10 High expansion foam devices; minimum capacity.

(a)On unattended underground equipment the amount of water delivered as high expansion foam for a period of approximately 20 minutes shall be not less than 0.06 gallon per minute per square foot of surface area of the equipment protected; however, the minimum total rate for any system shall be not less than 3 gallons per minute.
(b)On attended underground equipment, foam may be delivered by internal injection, inundation, or combination-type systems. Each system shall deliver water as foam for a minimum of 10 minutes. For internal injection, the rate of water application as high expansion foam shall be not less than 0.5 gallon per minute per hazardous location; however, the minimum total rate shall be not less than 2 gallons pe

Free access — add to your briefcase to read the full text and ask questions with AI

Nearby Sections

11

Cite This Page — Counsel Stack

Bluebook (online)
30 C.F.R. § 75.1107-10, Counsel Stack Legal Research, https://law.counselstack.com/cfr/30/75/75.1107-10.
View on eCFR ↗